摘要

In this work, sliding mode predictive control (SMPC) was applied to an air conditioning solar plant. The process has a variable time delay with non-minimum phase behavior, whose inverse response changes with the operating point. Disturbances are produced by changes in solar irradiation and solar collectors' inlet temperature. The algorithm combines the design technique of sliding mode control (SMC) with model-based predictive control (MPC). The SMPC showed a considerable robustness improvement with respect to MPC under experimental validation on a real plant and also showed an enhanced ability to handle set point changes and disturbance rejection.
机译:在这项工作中,将滑模预测控制(SMPC)应用于空调太阳能发电厂。该过程具有可变的时间延迟,具有非最小相位行为,其逆响应随工作点而变化。太阳辐射和太阳能集热器入口温度的变化会产生干扰。该算法将滑模控制(SMC)的设计技术与基于模型的预测控制(MPC)相结合。在实际工厂的实验验证下,SMPC相对于MPC表现出了显着的鲁棒性提高,并且还具有增强的设定值变化和干扰抑制能力。

著录项

  • 来源
    《Control Engineering Practice》 |2009年第6期|652-663|共12页
  • 作者单位

    Institute of Informatics and Applications, University of Girona, Campus Montilivi, Girona 17071, Spain Escuela de Ingenieria Electrica, Facultad de Ingenieria, Universidad de Los Andes, La Hechicera, Merida 5101, Venezuela;

    Escuela de Ingenieria Electrica, Facultad de Ingenieria, Universidad de Los Andes, La Hechicera, Merida 5101, Venezuela;

    Departamento de Ingenieria de Sistemas y Automatica, Universidad de Sevilla, Camino de Los Descubrimientos s, Sevilla 41092, Spain;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    non-minimum phase systems; model predictive control; sliding mode control; solar energy; time delay;