首页> 外文期刊>IEEE Transactions on Applied Superconductivity >Fault Current Limitation Characteristics of Bi-2212 Bulk Coil With Different Types of Shunt Coils
【24h】

Fault Current Limitation Characteristics of Bi-2212 Bulk Coil With Different Types of Shunt Coils

机译:不同类型并联线圈的Bi-2212散装线圈故障电流限制特性

获取原文
获取原文并翻译 | 示例
           

摘要

We investigated fault current limitation characteristics of a resistive superconducting fault current limiter (SFCL) which consists of a Bi-2212 bulk coil and a shunt coil. For the experiments, different types of shunt-coils which had the same impedance were prepared. One group had high resistance, and the others were designed to have high inductance. The effects of the impedance component variation on current limitation characteristics of the SFCL were compared with each other. The test results showed that the SFCLs of both groups successfully limited the fault current of 7 ${rm kA}_{rm rms}$ to below 5 ${rm kA}_{rm p}$ right after the fault occurred. The SFCLs with a shunt coil of higher inductance quenched more uniformly, but had a high voltage spike by $Ldi/dt$ at the first half cycle after fault. On the other hand, the ones with higher resistance quenched comparatively less uniformly, but the voltage spike was much smaller. The impedance of the shunt coil is being optimized, taking into consideration stability, insulation, its effect on the circuit and other factors.
机译:我们研究了由Bi-2212大容量线圈和并联线圈组成的电阻型超导故障限流器(SFCL)的故障限流特性。为了进行实验,准备了具有相同阻抗的不同类型的并联线圈。一组具有高电阻,另一组被设计为具有高电感。相互比较了阻抗分量变化对SFCL电流限制特性的影响。测试结果表明,两组SFCL都在故障发生后立即将故障电流7 $ {rm kA} _ {rm rms} $限制在5 $ {rm kA} _ {rm p} $以下。带有较高电感的并联线圈的SFCL更均匀地淬灭,但在故障后的前半个周期内出现$ Ldi / dt $的高电压尖峰。另一方面,电阻较高的淬火相对较不均匀,但电压尖峰小得多。考虑到稳定性,绝缘性,对电路的影响和其他因素,正在优化并联线圈的阻抗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号