Winding overheating is a common fault in a transformer. To detect the temperature, the most widely used method is a point-type measurement, but traditional measurement methods cannot obtain the whole temperature distribution in a transformer. Taking this into consideration, a new method with which to measure the temperature of transformer windings was proposed. Based on Raman scattering, a new fibre-optic composite winding model was developed. The feasibility of the model was verified by electrical as well as temperature, field simulation and power frequency resistance testing. To assess the practicality and accuracy of the new model, a distributed optical fibre temperature measurement platform was built, and a series of experiments were designed. According to the data collected, the temperature measurement error based on the method could be limited to 1 °C while the positioning accuracy error was within 1 m, which meant that the new approach can satisfy the requirements of transformer winding temperature measurement and locate hot spots in the winding.
机译:绕组过热是变压器的常见故障。为了检测温度,最广泛使用的方法是点型测量,但是传统的测量方法无法获得变压器中的整个温度分布。考虑到这一点,提出了一种测量变压器绕组温度的新方法。基于拉曼散射,开发了一种新的光纤复合绕组模型。通过电气,温度,现场模拟和工频电阻测试,验证了该模型的可行性。为了评估新模型的实用性和准确性,建立了分布式光纤温度测量平台,并设计了一系列实验。根据采集的数据,该方法的温度测量误差可以限制在1°C,而定位精度误差在1 m以内,这意味着该新方法可以满足变压器绕组温度测量和定位热点的要求。在缠绕。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号