首页> 美国卫生研究院文献>Materials >Analysis of the Occurrence of Thermal Bridges in Several Variants of Connections of the Wall and the Ground Floor in Construction Technology with the Use of a Hemp–Lime Composite
【2h】

Analysis of the Occurrence of Thermal Bridges in Several Variants of Connections of the Wall and the Ground Floor in Construction Technology with the Use of a Hemp–Lime Composite

机译:麻灰复合材料在施工技术中墙体与地面连接的几种变型中热桥的发生分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This article analyses the connection of the two types of floors on the ground (floors on joists and self-supporting floors), with the external wall made of a hemp–lime composite for the occurrence of thermal bridges. Several factors that may affect the heat transfer in the junction were taken into account: the level of the floor on the ground, the wall thickness, the thermal conductivity of the composite, and the location of the timber frame construction. The technology of using hemp and lime is relatively new, and there is a lack of such analyses in the literature. The two-dimensional (2D) heat-transfer in the described construction joints was analyzed based on the finite-element method with the use of the THERM 7.4 software. The results were presented as averaged and linear thermal transmittance coefficients dependent on the above mentioned factors. The possibility of surface condensation was also checked. The differences in the values of the thermal transmittance of the junction between the two variants of ground floors reached around 0.13%–1.67% and the values of linear thermal transmittance factor reached approximately 2.43%–10.13%. The junctions with the highest floor level showed a decrease in the thermal transmittance value by about 3.00%–5.77% and in the linear thermal transmittance, by about 21.98%–53.83%, compared to the junctions with the lowest floor level. Calculations showed that almost all analyzed junctions are free from surface condensation causing mould growth, because the minimum temperature factors f0.25 were higher than 0.78 (except for junctions with the lowered floor levels). The junction with a floor on the timber joists showed better thermal parameters than the junction with a self-supporting floor in each of the analyzed variants. By increasing the level of floor insulation, it is possible to limit the thermal bridges and improve the thermal properties of the junction.
机译:本文分析了地面上两种类型的地板(托梁地板和自支撑地板)的连接情况,外墙是由麻灰复合材料制成的,用于发生热桥。考虑了可能影响接合处传热的几个因素:地面在地面上的水平,壁厚,复合材料的导热性以及木构架结构的位置。使用大麻和石灰的技术是相对较新的,并且在文献中缺乏这种分析。使用THERM 7.4软件,基于有限元方法分析了所描述的施工缝中的二维(2D)传热。结果表示为取决于上述因素的平均和线性传热系数。还检查了表面凝结的可能性。两种变体之间的接合处的热透射率值的差异达到约0.13%–1.67%,线性热透射率因子的值达到约2.43%–10.13%。与最低楼层的交汇处相比,楼层最高的交汇处的热透射率值降低了约3.00%-5.77%,线性传热率降低了约21.98%-53.83%。计算表明,几乎所有已分析的连接处都没有表面凝结而导致霉菌生长,因为最低温度因子f0.25高于0.78(地板水平较低的连接处除外)。在每个分析的变体中,与木托梁地板接合处的热参数均优于与自支撑地板接合处的热参数。通过增加地板的隔热水平,可以限制热桥并改善结的热性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号