首页> 中文期刊> 《等离子体科学和技术:英文版》 >Repeated Strike Process During Disconnector Operation in Ultra-High Voltage Gas-Insulated Switchgear

Repeated Strike Process During Disconnector Operation in Ultra-High Voltage Gas-Insulated Switchgear

         

摘要

Very fast transient over-voltage(VFTO),induced by disconnector operations in gasinsulated switchgears,has become the limiting dielectric stress at ultra-high voltage levels.Much work has been done to investigate single-strike waveforms of VFTO.However,little study has been carried out investigating the repeated strike process,which would influence VFTO significantly.In this paper,we carried out 450 effective experiments in an ultra-high voltage test circuit,and conducted calculations through the Monte Carlo simulation method,to investigate the repeated strike process.Firstly,the mechanism of the repeated strike process is proposed,based on the experimental results.Afterwards,statistical breakdown characteristics of disconnectors are obtained and analyzed.Finally,simulations of the repeated strike process are conducted,which indicate that the dielectric strength recovery speed and polarity effect factor have a joint effect on VFTO.This study enhances the understanding of the nature of VFTO,and may help to optimize the disconnector designed to minimize VFTO.