To explore the influence of heat reservoirs of total thermal capacity at high and low temperature side heat exchanger of an irreversible refrigeration cycle on the coefficient of performance,the cycle model is established. By using the irreversible thermodynamics,much progress had been made in the studies of thermal resistance,heat leak and irreversible factors on the cycle of the coefficient of performance. The analytical formula of coefficient of performance and the distribution ratio of total thermal capacity are derived when the total thermal capacity at high and low temperature side heat exchanger is a constant. The influences of cycle parameters and different kinds of irreversible factors on the coefficient of performance and the optimal distribution ratio are analyzed by numerical computation. The results indicate that the coefficient of performance increases with the increase of the total heat capacity,and decreases with heat leak and internal irreversible factors. Furthermore,the optimal distribution ratio of total thermal capacity,when coefficient of performance reaches the maximum value,only has a connection with the internal dissipation.