Intermittent new energy delivery requires increasing the flexibility of ultra-high voltage direct current(DC)power adjustment.Based on a converter steady-state model and a DC power model,the control angle constraints of a converter valve are relaxed for power regulation.In this paper,a flexible DC power control method based on a fixed tap changer position is proposed.The initial ratio of the converter transformer is optimized.The effects of the fixed-tap changer position control on the control angle,reactive power compensation,and commutation failure are analyzed.The new control method allows a DC system to operate at a large angle and increase the additional reactive power loss while improving the commutation security margin.Steady-state and electromagnetic transient simulations in the CIGRE test system verify the validity of the method proposed in this paper and the correctness of the analysis conclusions.