首页> 外文学位 >Pressure loss testing of saddle tap tees and a fabric air duct.
【24h】

Pressure loss testing of saddle tap tees and a fabric air duct.

机译:鞍形三通和织物风管的压力损失测试。

获取原文
获取原文并翻译 | 示例

摘要

Pressure loss tests were conducted on diverging and converging flow saddle tap tees per ASHRAE Standard 120 (2008). A power law curve-fit was used for diverging flow tees to correlate branch loss coefficients as a function of branch-to-common flow rate and area ratios. Likewise a logarithmic curve-fit model was used to correlate branch loss coefficients for converging flow tees as a function of branch-to-common flow rate ratio. The argument of the logarithmic function was corrected to account for the area ratio of the fitting. For both diverging and converging flows, main loss coefficients were correlated in terms of an inverse linear relationship with the straight-to-common flow rate ratio. Main loss coefficient data were largely independent of branch-to-common area ratio. The resulting coefficient of determination values ranged from 0.543 to 0.927, indicating a suitable degree of correlation.;Friction factors for a round non-porous fabric duct were measured per ASHRAE Standard 120 (2008). Two configurations were tested. In one instance an internal frame to maintain a round cross section when no air was flowing through the system was absent. For other tests a tubular steel frame was inserted through the entire length of the duct so as to maintain the duct shape in the absence of air flow. It is recommended that round fabric ducts lacking an internal support frame be categorized as “MEDIUM ROUGH" in the Duct Design chapter of the ASHRAE Handbook of Fundamentals. It is further recommended that round fabric ducts possessing a tubular steel internal support frame be categorized as "ROUGH" in the Handbook.
机译:根据ASHRAE Standard 120(2008)对分流和收敛流量鞍形三通进行了压力损失测试。幂律曲线拟合用于使三通分流,以使支路损耗系数与支路与普通流量和面积比的函数相关。同样,对数曲线拟合模型用于将汇流三通的支路损耗系数与支流与普通流量之比的函数相关。对数函数的参数已更正,以说明拟合的面积比。对于分流和会聚流量,主要损失系数都与直线流量与普通流量之比成反线性关系。主要损耗系数数据在很大程度上与分支与公用面积之比无关。所得的确定系数值在0.543至0.927的范围内,表明相关程度合适。根据ASHRAE Standard 120(2008)测量圆形无孔织物导管的摩擦系数。测试了两种配置。在一个实例中,当没有空气流过该系统时,没有一个保持圆形横截面的内部框架。对于其他测试,将管状钢制框架插入管道的整个长度,以便在没有气流的情况下保持管道的形状。在ASHRAE基础手册的风管设计一章中,建议将没有内部支撑框架的圆形织物风道归为“ MEDIUM ROUGH”。进一步建议将具有管状钢内部支撑框架的圆形织物风道归为“粗糙”。

著录项

  • 作者

    Nalla, Ananth Nag.;

  • 作者单位

    Tennessee Technological University.;

  • 授予单位 Tennessee Technological University.;
  • 学科 Engineering Mechanical.
  • 学位 M.S.
  • 年度 2011
  • 页码 67 p.
  • 总页数 67
  • 原文格式 PDF
  • 正文语种 eng