Performance of an air-based solar thermal system after twenty years of operation

机译:运转二十年后,基于空气的太阳能热系统的性能

获取原文
获取原文并翻译 | 示例

摘要

Investigations of a 20 year old air-based solar installation were made to quantify the degradation of system components as well as operation of the system as a whole. The current solar fraction of the system is extremely low at 13 percent. Experiments show a marked degradation in both the transmittance-absorbance product and the loss coefficient of the collector array. The pebble beds were also subject to high losses through the building foundation as well as non-uniform flows caused by an obstruction int he upper pleum. The effects of these degradations would lower the solar fraction from an optimum of 44 to 32 percent. The low value for the current performance is attributed to poor sensor placement and the control strategy.
机译:对20年之久的基于空气的太阳能装置进行了调查,以量化系统组件的退化以及整个系统的运行情况。该系统当前的太阳能比例极低,仅为13%。实验表明,透射率-吸光率乘积和收集器阵列的损耗系数均明显降低。卵石床还受到建筑物基础的巨大损失,以及由于上部胸腔阻塞而造成的流量不均匀。这些退化的影响将使太阳能分数从最佳的44%降低到32%。当前性能的低值归因于不良的传感器放置和控制策略。