首页> 外文会议>Proceeding of the 1995 IEEE 5th international conference on conduction and breakdown in solid dielectrics >Partial discharge pulse characteristics of electrical trees in XLPE cable insulation
【24h】

Partial discharge pulse characteristics of electrical trees in XLPE cable insulation

机译:交联聚乙烯电缆绝缘中电树的局部放电脉冲特性

获取原文
获取原文并翻译 | 示例

摘要

Rise time, fall time, width, amplitude and repetition rate of PD pulses have been measured as a function of tree growth time in small samples of XLPE cable using a UWB detection method. The results indicate that as the tree grows rise time, fall time and pulse width increase. Over the same period, the magnitudes tend to become more concentrated about a single value. These data appear to be consistent with the appearance of a single channel close to failure.
机译:已经使用UWB检测方法测量了小尺寸的XLPE电缆中PD脉冲的上升时间,下降时间,宽度,幅度和重复率与树木生长时间的关系。结果表明,随着树的生长,上升时间,下降时间和脉冲宽度都会增加。在同一时期,幅度趋于变得更集中于单个值。这些数据似乎与接近故障的单个通道的外观一致。