On October 31, 2006, the Homestake Pipeline experienced a catastrophic failure. This 66-inch (1680 millimeter) diameter, 46-mile (74-kilometer) long, prestressed concrete (non-cylinder) pipeline (PCP) traverses Colorado's mountains and provides roughly 60 percent of the raw water for the Cities of Aurora and Colorado Springs. The Homestake Water Project, operator of the pipeline, had completed the first year of inspection in a multi-year condition assessment program and this inspection had stopped approximately 1 mile short of the future failure site.rnThe failure occurred on the PCP at the transition point between steel and PCP pipe. The nature and apparent cause of the failure provide insight to potential vulnerabilities at similar transition points on the Homestake Pipeline and the importance of circumferential cracking in non-cylinder pipelines. The potential for failures at joint end-areas, which are "blind spots" for electromagnetic inspection, suggest caution be used when drawing conclusions from such inspections. The failure cause and the subsequent repair modified the planning for the subsequent years of condition assessment and resulted in a revised repair spool configuration and repair procedure.
机译:2006年10月31日,霍姆斯特克管道发生了灾难性的故障。直径66英寸(1680毫米),46英里(74公里)长的预应力混凝土(非圆筒)管道(PCP)穿越科罗拉多州的山脉,并为奥罗拉和科罗拉多州的城市提供大约60%的原水温泉。管道运营商霍姆斯特克水项目(Homestake Water Project)已在多年状态评估计划中完成了第一年的检查,并且该检查已在距离未来故障站点约1英里的距离处停止。rn故障发生在过渡点的PCP上在钢管和PCP管道之间。故障的性质和明显原因使您可以洞悉Homestake管道上类似过渡点处的潜在漏洞,以及非圆柱管道中周向裂缝的重要性。关节末端区域的潜在故障是电磁检查的“盲点”,建议在从此类检查得出结论时要格外小心。故障原因和随后的维修修改了随后几年状态评估的计划,并导致修订的维修阀芯配置和维修程序。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号