首页> 外文会议>International Symposium on Discharges and Electrical Insulation in Vacuum >Interruption performance at frequency 50 or 60Hz for generator breaker equipped with vacuum interrupters
【24h】

Interruption performance at frequency 50 or 60Hz for generator breaker equipped with vacuum interrupters

机译:用于发电机断路器的频率50或60Hz的中断性能配备真空中断器

获取原文

摘要

Vacuum interrupters are serving worldwide in distribution circuits, meeting the electrical and mechanical requirements specified in the IEC and/or ANSI standards for low and medium voltage applications. Generator circuits require special generator circuit-breakers and are tested according to IEC 62271-37.013/ANSI/IEEE C37.013. Traditionally, generator circuit-breakers have been very large devices based on air- or SF6- blast interruption technology. Over the last 35 years, the short circuit interruption performance of vacuum interrupters has been dramatically increased due to continuous development, especially of contact system design and contact materials. These improvements allow the application of vacuum interrupter technology to generator circuit-breakers. Three phase vacuum circuit-breakers are available for this application in generator circuits at 50 and 60 Hz. To fulfil the required short circuit interruption ability, the test has to be performed at 50Hz for IEC markets and at 60Hz / 50Hz for ANSI markets. When the short circuit interruption ability is tested at 50Hz, the results can be transferred to 60Hz because the arcing time is reduced, while the di/dt is slightly steeper at current zero. Four main factors related to vacuum technology are investigated: The influence of the arcing time duration before current zero (CZ), the transferred charge I x dt, di/dt steepness at CZ, and finally the transient recovery voltage (TRV).
机译:真空中断器在全球范围内在配送电路中提供服务,满足IEC和/或ANSI标准中规定的电气和机械要求,用于低频和中压应用。发电机电路需要特殊的发电机断路器,并根据IEC 62271-37.013 / ANSI / IEEE C37.013进行测试。传统上,发电机断路器基于空气或SF6-爆破中断技术非常大的设备。在过去的35年中,由于连续开发,特别是接触系统设计和接触材料,真空中断器的短路中断性能已经显着增加。这些改进允许将真空断路器技术应用于发电机断路器。在50和60Hz的发电机电路中提供三相真空断路器。为了满足所需的短路中断能力,必须在50Hz的IEC市场和60Hz / 50Hz的测试进行测试,用于ANSI市场。当在50Hz测试短路中断能力时,结果可以将结果转移到60Hz,因为电弧时间减小,而DI / DT在电流零时略陡。研究了与真空技术有关的四个主要因素:电弧旋转延时在电流零(CZ)之前的影响,CZ的转移电荷I x DT,DI / DT陡度,最后是瞬态恢复电压(TRV)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号