首页> 外文会议>International Conference on Electricity Distribution >Qualification tests performed on composite insulators for 132-150 kV overhead lines
【24h】

Qualification tests performed on composite insulators for 132-150 kV overhead lines

机译:在复合绝缘子上进行了132-150 kV架空线进行的验证试验

获取原文

摘要

Composite insulators may be prone in service to damage of the external housing (tracking, split, erosion, chalking) and of the core (mechanical failure). An IEC Standard was issued that ENEL applied, with some adaptation and implementation, in performing the insulator qualification. As for a tracking and erosion test, two alternative procedures are given by the IEC Standard to reproduce the service stresses in severe ambients. To cover the risk of fractures in service due to fatigue and stress corrosion of the insulator core, ENEL studied and defined a mechanical-chemical long term test. The authors describe the results of the above mentioned tests obtained on a few types of composite insulators of the latest production. For the two insulator types that have now passed all the planned tests, a pilot service experience is going to start on 132-150 kV line sections chosen all over Italy.
机译:复合绝缘体可以俯卧,以损坏外壳(跟踪,分裂,腐蚀,粉笔)和核心(机械故障)。 发出了IEC标准,旨在掌握某种适应和实施,在执行绝缘子资格时。 至于跟踪和侵蚀测试,IEC标准给出了两种替代程序,以重现严重的环境中的服务应力。 为了涵盖抗疲劳和疲劳的疲劳骨折的风险,由于绝缘体芯的疲劳和应力腐蚀,eNEL研究和定义了机械化学的长期试验。 作者描述了在最新生产的几种复合绝缘体上获得的上述测试的结果。 对于现在通过所有计划测试的两种绝缘体类型,试点服务体验将于132-150 kV线路部分选中的意大利。