首页> 外文会议>GRC 2013 >Performance Test of a Ground-Air Heat Exchange Fresh Air System for an Office Building in Tangshan
【24h】

Performance Test of a Ground-Air Heat Exchange Fresh Air System for an Office Building in Tangshan

机译:唐山办公楼地下空气热交换新空气系统的性能试验

获取原文

摘要

A fresh air system using ground-air heat exchangers (GAHEs) was built for an office building in Tangshan, and its actual performance during the operation period in summer and winter, were tested and analyzed. Results showed that the present system Was reliable. The maximum indoor CO_2 concentfation ranged from 600-700ppm, satisfying the requirements of indoor air quality, For a typical operation condition, the underground heat exchange rate per the internal surface area of GAHEs reached 44.2W/m~2 in summer and 90.9W/m~2 in winter, and the corresponding daily-average heat exchange efficiency was 0.72 and 0.84, respectively. The present results are useful for further optimization of GAHE systems built under similar climate conditions.
机译:采用地面空气热交换器(Gahes)的新空气系统建于唐山的办公楼,并在夏季和冬季运营期间的实际表现进行了测试和分析。结果表明,本系统可靠。最大的室内CO_2浓缩量为600-700ppm,满足室内空气质量的要求,对于典型的操作条件,GAHES内部表面积的地下热汇率达到44.2W / m〜2,夏季和90.9W /冬季M〜2,相应的每日平均热交换效率分别为0.72和0.84。目前的结果对于在类似气候条件下建造的Gahe系统进一步优化。