首页> 外文会议>International Conference on Mechanical Engineering and Intelligent Systems >Research On The Fault Tripping Criteria Of Stability Control Device Adapting To AC-DC Hybrid Power Grid
【24h】

Research On The Fault Tripping Criteria Of Stability Control Device Adapting To AC-DC Hybrid Power Grid

机译:适应AC-DC混合动力电网的稳定控制装置的故障跳闸标准研究

获取原文

摘要

The fault of AC bus in HV (high-voltage) AC-DC hybrid system can cause consequential commutation failure in converter station, and it affect the correct operation of the current stability control device. The mechanism of phase commutation failure is explained in the paper, and the variation of each electrical quantity in AC/DC system during phase commutation failure is analyzed. In addition, it puts forward the new fault tripping criteria in stability control device which adapts to the fault characteristic of AC power grid nearby converter station and based on the comparison between phase voltage and sequence voltage, and sets up the hybrid system containing three DC transmission line under PSCAD/EMTDC to verify the effectiveness of the criteria.
机译:HV(高压)AC-DC混合系统中交流总线的故障可能导致转换器站中的后续换向故障,并影响电流稳定控制装置的正确操作。 分析了相换向失败的机制,分析了相位换向失败期间AC / DC系统中的每个电量的变化。 此外,它提出了稳定控制装置中的新故障跳闸标准,它适应交流电网附近的转换器站的故障特性,并基于相电压和序列电压之间的比较,并建立了包含三个直流传输的混合系统 在PSCAD / EMTDC下线验证标准的有效性。