首页> 外文会议>IEEE Interantional Conference on Industrial Technology >Regenerative PWM Source for Power Transformer Loading Tests
【24h】

Regenerative PWM Source for Power Transformer Loading Tests

机译:电力变压器加载测试的再生PWM源

获取原文

摘要

Most of power transformers, before being commercialized, must undertake a series of tests with the objective of analyzing their operational behavior under real operating conditions. Such tests sometimes demand a high amount of power increasing significantly their costs. The paper presents a proposed system which allows testing in closed loop, reducing the energy consumption to the natural losses of the equipment, thus constituting a regenerative system. A VSI-based test environment for power transformers where controlled active and reactive power can be supplied is designed, simulated and realized as a 50KVA- prototype. Special care is taken concerning the ac- filters in order to keep the harmonics within the limits set by standards valid for testing of power transformers. The simulation and experimental results show that the prototype fulfills the given requirements.
机译:在商业化之前,大多数电力变压器必须采取一系列测试,其目的是在实际操作条件下分析其运行行为。这种测试有时需要大量的功率显着提高其成本。本文介绍了一个允许在闭环中测试的建议系统,将能量消耗降低到设备的自然损失,从而构成再生系统。设计,模拟和实现为50kva-原型设计,模拟和实现了基于电力变压器的基于电力变压器的测试环境。有关AC-滤波器的特殊护理,以便将谐波保留在标准设置的限制范围内,该限制适用于测试电力变压器。模拟和实验结果表明,原型符合给定的要求。