To test and study the performance of a quasi two-stage compression heat pump system coupled with ejectors, three kinds of ejectors have been designed, and heat pump prototypes have been set up with different ejectors. When condensation temperature keeps at 45°C and evaporation temperature varies from -8°C to -25°C, the performance of each heat pump prototype has been comprehensively tested. The experimental results demonstrate that the heat pump system coupled with ejector has better performance than the quasi two-stage heat pump system under the design conditions, but its performance will decrease under the off-design conditions. The heat pump system coupled with an optimized ejector can obtain an excellent performance in a wide range of operation conditions, and its heating COP can be about 10% higher than that of the heat pump system without ejector.
机译:为了测试和研究与喷射器连接的准两级压缩热泵系统的性能,已经设计了三种喷射器,并使用不同的喷射器建立了热泵原型。当冷凝温度保持在45°C时,蒸发温度从-8°C变化至-25°C时,每个热泵原型的性能都已全面地测试。实验结果表明,在设计条件下,与喷射器连接的热泵系统具有比准二级热泵系统更好的性能,但其性能在非设计条件下会降低。连接有优化喷射器的热泵系统可以在宽范围的操作条件下获得优异的性能,并且其加热COP可以比没有喷射器的热泵系统高约10%。