首页> 外文会议>Annual international conference on incineration and thermal treatment technologies >INCINERATION COMBUSTION CONTROL USE OF FAST SENSORS TO MINIMIZE AWFCOS
【24h】

INCINERATION COMBUSTION CONTROL USE OF FAST SENSORS TO MINIMIZE AWFCOS

机译:焚烧燃烧控制使用快速传感器以最小化AWFCOS

获取原文

摘要

The MACT Rule puts a high priority on minimizing exceedances and many units will need combustion control enhancements to meet the Rule. In situ oxygen analyzers can give 1-second response times. An alternative process variable for fast incineration combustion control is gas temperature, which can be indicated almost instantly by an optical pyrometer. The gas temperature, combined with oxygen concentration, can provide fast control of incineration combustion conditions to minimize CO or THC exceedances. If needed, direct oxygen injection can provide a final ensurance that the oxygen level is kept above the key minimum level to maintain good combustion conditions. Reduced AWFCOs can pay off in increased on-feed time that more than pays for the enhanced control system.
机译:MACT规则对最小化的优先级,并且许多单位需要燃烧控制增强以满足规则。原位氧气分析仪可以提供1秒的响应时间。用于快速焚烧燃烧控制的替代过程变量是气体温度,可以通过光学高温计几乎立即指示。与氧浓度相结合的气体温度可以提供快速控制焚烧燃烧条件,以最小化CO或THC超标。如果需要,直接氧注射可以提供最终的确保,即氧气水平保持在关键最小水平以保持良好的燃烧条件。减少的AWFCO可以在增加的进给时间增加的情况下,超过增强控制系统的费用。

著录项