首页> 外文会议>IEEE Power Energy Society General Meeting >An Efficient Surge Arrester Placement Strategy to Improve the Lightning Performance of Long Transmission Line
【24h】

An Efficient Surge Arrester Placement Strategy to Improve the Lightning Performance of Long Transmission Line

机译:有效的避雷器放置策略,提高长传输线的雷电性能

获取原文

摘要

Installing surge arresters would enhance the transmission system reliability but it comes with extra capital expenditure. In order to determine the most efficient and cost-effective surge arrester configuration of the protected transmission line, a novel surge arrester placement strategy is proposed in this paper. According to the characteristic of the transmission line tower footing resistance, the entire transmission line can be divided into several line sections. Each line section consists of the towers which have similar footing resistance. Two different designs are considered for transmission line lightning protection: (i) equip different numbers of surge arresters on selected phase of each tower; (ii) equip surge arresters on all phases of selected towers. By varying the number of towers to be equipped or the number of phases to be equipped with surge arresters, the threshold voltage for line flashover is used to evaluate different surge arrester installation configurations.
机译:安装浪涌避雷器将提高传输系统的可靠性,但它具有额外的资本支出。为了确定保护传输线的最有效和经济高效的避雷器配置,本文提出了一种新颖的避雷器放置策略。根据传输线塔脚踏性的特性,整个传输线可以分成几个线路部分。每个线部分由具有相似的距离电阻的塔。考虑两种不同的设计用于传输线雷电保护:(i)在每个塔的所选阶段上装备不同数量的浪涌避雷器; (ii)在选定塔的所有阶段配备浪涌避雷器。通过改变要装备的塔的数量或配备浪涌避雷器的阶段的数量,用于对线闪过透档的阈值电压用于评估不同的电涌避雷器安装配置。