Revenue metering error caused by induced voltage from adjacenttransmission lines

机译:由相邻感应电压引起的收入计量错误传输线

获取原文

摘要

A large zero sequence voltage was found to have been induced ontoa 138 kV line from adjacent 500 kV lines where these share the sametransmission right-of-way. This zero sequence voltage distorted the2.5-element revenue metering schemes used for two large industrialcustomers supplied directly from the affected 138 kV line. As a result,these two customers were overcharged, on average, approximately 3.5% for15 years. The work done to trace the origins of the zero sequencevoltage and quantify the metering error is described. Customer refundswhich, in the end, totalled $4 million are calculated
机译:发现一个很大的零序电压被感应到 从相邻的500 kV线路共享一条相同的138 ​​kV线路 传输路权。这个零序电压使 用于两个大型工业的2.5元素收入计量方案 客户直接从受影响的138 ​​kV线路供电。因此, 这两个客户平均多收了3.5% 15年。追踪零序列起源的工作 电压和量化计量误差的描述。客户退款 最后计算得出的总额为400万美元