首页> 外文会议>Electrical Insulation Conference >Improvements in Direct Current Stator Winding Insulation Testing
【24h】

Improvements in Direct Current Stator Winding Insulation Testing

机译:直流定子绕组绝缘测试的改进

获取原文

摘要

Direct Current (DC) high voltage testing is frequently used to assess the condition of stator windings. The list of the reasons why DC tests may be preferred over alternating 50 Hz or 60 Hz voltage tests is long: smaller size of the test equipment, fewer partial discharges, less risk of damage in the case of very poor insulation quality. Different direct current test methods are possible such as DC HIPOT, polarization index test, ramped voltage test, uniform time and graded time voltage step test, insulation profiling, etc. Since the traditional DC hi-pot test is not a diagnostic test (the result of the test is either PASS or FAIL), an improved method of DC testing using ramped direct high voltage was introduced by Bruce McHenry in 1964 [6] and this paper describes the differences between the two ramped direct-high voltage methods proposed in IEEE 95.
机译:直流(DC)高压测试经常用于评估定子绕组的条件。 DC测试的原因清单可以优选通过交替的50Hz或60 Hz电压测试是长的:测试设备的较小尺寸,部分放电少,绝缘质量非常差的情况下损坏的风险较低。不同的直流试验方法,如DC Hipot,偏振指数测试,斜坡电压测试,均匀的时间和分级时间电压步骤测试,绝缘分析等,因为传统的DC Hi-Pot测试不是诊断测试(结果测试要么是通过或失败),由Bruce Mchenry在1964年引入了使用斜坡直接高压的改进方法[6],本文介绍了IEEE 95中提出的两个斜坡直接高压方法之间的差异。

著录项