CO_2 vapor compression systems

机译:CO_2蒸气压缩系统

获取原文

摘要

According to the Regulation implementing the European Directive 2009/125/EC, from the year 2018, chillers with a rated cooling capacity not exceeding 2 MW must fulfil a series of "ecodesign" requirements to be placed on the market and/or put into service. Carbon dioxide (CO_2) as working fluids is, at least initially, not the best solution for air conditioning or chiller units due to its thermophysical properties. However, it is the purpose of this work to demonstrate that CO_2 could be a suitable refrigerant in chillers when certain design changes are implemented to the refrigeration system of the chiller. Simulations have shown that an improvement on the performance of chillers with CO_2 is obtained if ejectors are introduced to unload the compressors of the CO_2 unit. Applying the available expansion work within an ejector lifts the suction pressure of the compressors significantly. Experimental tests have been performed with the Su-perSmart-Rack facility at NTNU/SINTEF. The operation conditions were specified in the aforementioned 'ecodesign' regulation to demonstrate that CO_2 chiller systems can actually fulfil the requirements.
机译:根据实施欧洲指令2009/125 / EC的法规,从2018年开始,额定制冷量不超过2兆瓦的冷水机必须满足一系列“生态设计”要求,才能投放市场和/或投入使用。 。由于二氧化碳(CO_2)的热物理性质,至少在最初,它不是用于空调或制冷机的最佳解决方案。但是,这项工作的目的是证明,当对制冷机的制冷系统进行某些设计更改时,CO_2可能是制冷机中的合适制冷剂。仿真表明,如果引入喷射器以卸载CO_2单元的压缩机,则具有CO_2的冷却器的性能将得到改善。在喷射器内进行可用的膨胀功可显着提升压缩机的吸入压力。已经使用NTNU / SINTEF的Su-perSmart-Rack设备进行了实验测试。在上述“生态设计”法规中指定了运行条件,以证明CO_2冷却器系统可以真正满足要求。