首页> 外文会议> >On-site Detecting Method for the Loss Characteristic in 110kV Power Transformer
【24h】

On-site Detecting Method for the Loss Characteristic in 110kV Power Transformer

机译:110kV电力变压器损耗特性的现场检测方法

获取原文

摘要

The loss characteristic of power transformer can reflect its working condition, which is related to the safety and stabilization of the power system. The off-line test needs to shut down the transformer, affecting the continuity of power supply and it cannot reflect real status of transformer. In this paper, a new on-site method supplied by electric grid for the loss characteristic of power transformer is designed. Besides, considering the spectrum leakage and picket fence effect in the signal processing, a developed interpolation algorithm with Blackman-Harris window is applied. Based on the method, an onsite measuring system for the load and no-load losses of transformer is designed. Furthermore, issues of no-load current measurement accuracy, synchronism of signal acquisition and signal interference are solved. Finally, the no-load and load losses on-site tests are carried out in substation. It is proved that the onsite measuring system is feasible.
机译:电力变压器的损耗特性可以反映其工作状态,这关系到电力系统的安全性和稳定性。离线测试需要关闭变压器,影响电源的连续性,不能反映变压器的真实状态。本文针对电力变压器的损耗特性,设计了一种新的由电网提供的现场方法。此外,考虑到信号处理中的频谱泄漏和栅栏效应,应用Blackman-Harris窗插值算法进行了改进。基于该方法,设计了一种变压器有载和无载损耗的现场测量系统。此外,解决了空载电流测量精度,信号采集同步和信号干扰等问题。最后,在变电站进行空载和失载现场测试。实践证明,该现场测量系统是可行的。