The traditional transformer respirator lacks the detection means, cannot realize the long-distance monitoring, and must carry on the regular inspection through the running staff to determine its state. This paper introduces a method of automatic detection of transformer respirator based on image processing with the aid of the intelligent inspection robot on-site shooting, returning the transformer respirator device image, using the digital image processing technology for color histogram analysis of the picture, and last making decisions to determine whether the need to replace the discoloration of silica gel. This method not only does not require any requirement for the structure of the transformer respirator, but also does not require any sensor device, thus greatly reducing the detection cost of the transformer respirator, both convenient and practical.
机译:传统的变压器呼吸器缺乏检测手段,无法实现远程监控,必须通过运行人员进行定期检查以确定其状态。本文介绍了一种基于智能检测机器人现场拍摄的图像处理自动检测变压器呼吸器的方法,返回变压器呼吸器设备的图像,使用数字图像处理技术对图片进行颜色直方图分析,以及最后做出决定,以确定是否需要更换硅胶变色。该方法不仅不需要对变压器呼吸器的结构进行任何要求,而且不需要任何传感器装置,从而大大降低了变压器呼吸器的检测成本,既方便又实用。