首页> 外文会议>Structural Stability Research Council annual stability conference >Dynamic Stability of Deep and Slender Wide-Flange Steel Columns - Full Scale Experiments
【24h】

Dynamic Stability of Deep and Slender Wide-Flange Steel Columns - Full Scale Experiments

机译:细长的宽法兰钢柱的动态稳定性-全面实验

获取原文

摘要

In North America, a common design practice for steel frame buildings with perimeter steel special moment frames (SMFs) is to employ deep and slender wide-flange steel columns (i.e., range of column depth, d > 16 inches). Till recently, very little was known regarding the hysteretic behavior of such members because of lack of available experimental data. This paper discusses selective findings from a full-scale testing program that was conducted at Ecole Polytechnique Montreal with the use of a 6-degree-of-freedom experimental setup. The testing program investigated the cyclic behavior of 10 full-scale beam-columns. The specimens had a depth of 24 inches (i.e., W24×146 and W24×84 cross-sections) and were subjected under various lateral-loading protocols coupled with constant compressive axial load. The boundary conditions of the specimens simulated a fixed support at the column base and a flexible boundary at the column top end to mimic the flexibility of a beam-to-column connection at the floor level. The tested specimens represented typical interior first-story columns in mid-rise steel SMFs. This paper summarizes the main observations related to the effect of local and global slenderness ratios on the cyclic behavior of beam-columns. The effect of bidirectional lateral loading on the dynamic stability of beam-columns is also addressed. Observations related to the effect of the employed loading history as well as the lateral bracing force design requirements on steel wide-flange beam-columns are also provided based on the available experimental results.
机译:在北美,对于具有周边钢特殊矩框架(SMF)的钢框架建筑物,常见的设计惯例是采用深而细的宽翼缘钢柱(即柱深度范围d> 16英寸)。直到最近,由于缺乏可用的实验数据,人们对此类构件的滞后行为知之甚少。本文讨论了使用6自由度实验装置在蒙特利尔Ecole Polytechnique进行的全面测试程序中的选择性发现。测试程序研究了10个满量程梁柱的循环行为。样品的深度为24英寸(即W24×146和W24×84横截面),并经受各种侧向载荷方案并施加恒定的轴向压缩载荷。样品的边界条件模拟了柱基处的固定支撑和柱顶端处的柔性边界,以模拟地板水平的梁柱连接的柔性。测试的样品代表了中层钢SMF中典型的内部第一层柱。本文总结了与局部和整体细长比对梁柱循环行为影响有关的主要观察结果。还解决了双向横向荷载对梁柱动力稳定性的影响。根据可获得的实验结果,还提供了与所采用的载荷历史以及横向支撑力设计要求对钢制宽法兰梁柱相关的观察结果。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号