The paper presents an example of modeling high-voltage line with classical columns and pillars compacted with the same lines and testing out the model in the programming tool DIgSILENT with actual measured data for Single Line to Ground Fault with the use of ARs. The parameters of the classical and compacted 400 kV transmission line are entered into the model in the example of 400 kV line Tuzla 4 - Vis?egrad, and Single Line to Ground Fault was simulated and compared with the actual measured data. Afterwards, lines with classical columns and pillars compacted with the lines were compared and assessed if a readjustment of distance protection on the line is necessary. The SIEMENS numerical distance relay 7SA was used.
机译:本文介绍了使用相同线路压实的经典柱和支柱建模高压线路的示例,并在使用ARS使用ARS的单线与地面故障的实际测量数据中测试模型。在400 kV线Tuzla 4 - VisΔegrad的示例中输入了经典和压实的400kV输电线路的参数,并模拟了单线与地面故障进行模拟,并与实际测量数据进行比较。然后,比较具有古典柱和用线压缩的柱子的线路,并且如果需要在线上的距离保护,则评估。使用西门子数值距离继电器7SA。