首页> 外文会议>IEEE Electric Ship Technologies Symposium >Limiting hull touch voltages in large power shore connection systems during phase-to-ground faults: A solution proposal
【24h】

Limiting hull touch voltages in large power shore connection systems during phase-to-ground faults: A solution proposal

机译:在相接地故障期间限制大型岸电连接系统中的船体接触电压:解决方案

获取原文

摘要

High Voltage Shore Connection (HVSC) is a technical solution to supply ships at berth in an economic way while reducing air pollution in city ports. The increased power demand of modern cruise ships may reach several tens of MVA, requiring a primary port voltage supply at voltage >100 kV. When a phase-to-ground fault arises on the HV side, safety problems due to increasing ship hull touch voltage may arise. A possible solution is proposed in this paper, based on an HV/HV y-Δ-y transformer with secondary resistance grounded neutral in the distribution power supply utility substation, with the aim to reduce phase-to-ground fault current at port.
机译:高压岸电连接(HVSC)是一种技术解决方案,可以经济地向泊位提供船舶,同时减少城市港口的空气污染。现代游轮增加的功率需求可能达到数十MVA,需要电压> 100 kV的主端口电压供应。当在HV侧发生相接地故障时,可能会出现由于船体接触电压升高而引起的安全问题。本文提出了一种可能的解决方案,该方案基于配电网公用变电站中具有次级电阻接地零线的HV / HVy-Δ-y变压器,目的是减少端口的相接地故障电流。