The present study aimed to improve a model to predict thermal performance of a heat pipe heat exchanger (HPHX) as pre-heater of the absorption system. The prediction was performed by utilizing thermal resistance and e-NTU method. Numerical modeling used an effective thermal conductivity (k_(eff)) without using measured data. Temperature profiles around heat pipes of the HPHX were predicted and compared with measured data. They agreed within the maximum deviation of 16 %. Thermal performances of the HPHX were predicted with the measured data within approximately 4 %. Calculated heat transfer coefficients for the evaporator of the heat pipe showed the similar with the values predicted by the literature correlation, while those inside the condenser of the heat pipe showed larger than the values predicted by the literature correlation.
机译:本研究旨在改进一种模型,以预测作为吸收系统预热器的热管热交换器(HPHX)的热性能。通过利用热阻和e-NTU方法进行预测。数值建模使用有效导热系数(k_(eff)),而不使用测量数据。可以预测HPHX热管周围的温度曲线,并将其与测量数据进行比较。他们同意最大偏差为16%。预测HPHX的热性能,测得的数据在4%以内。计算出的热管蒸发器的传热系数与文献相关性预测的值相似,而热管冷凝器内部的传热系数大于文献相关性预测的值。