首页> 外文会议>MIC;International Conference on Measurement, Information and Control >Test for error of current transformer based on low-voltage extrapolation method
【24h】

Test for error of current transformer based on low-voltage extrapolation method

机译:基于低压外推法的电流互感器误差测试

获取原文

摘要

The extrapolation method for the error test of the current transformer is to tests the current transformer on-site as a voltage transformer with the same error, which firstly test the error, admittance and other parameters of the trans-former at 200%to 1000%rated voltage or current, then test the admittance at 1%to 120%rated voltage or current, and finally achieves the error through the calculation. Its application will bring a great influence on the test of the current transformer on-site.
机译:电流互感器误差测试的外推方法是将电流互感器作为具有相同误差的电压互感器进行现场测试,首先在200%至1000%的范围内测试变压器的误差,导纳和其他参数。额定电压或电流,然后在1%至120%额定电压或电流下测试导纳,最后通过计算得出误差。它的应用将对电流互感器的现场测试产生很大的影响。