The paper presents the results of the researches on the service behaviour of the precast centrifuged hollow reinforced concrete elements (columns, beams and supports) for sustaining of electrical equipments in the electric transformer stations of 110...400 kV, after 30-40 years of service, in respect of the damages induced by the corrosive action of aggressive agents. The corrosion-induced damages have been favoured/increased by existence of initial execution malfunctions, deteriorations appeared during the storage, transport and montage of the elements and by absence of efficient intervention measures and anti-corrosion protection of these elements. There were pointed out the corrosive action effects of the aggressive agents on the centrifuged reinforced concrete elements in the electric transformer stations placed both in aggressive environments in power and chemical industries, as well as in electrical network urban units specific aggressive environments. Colour photos illustrate the characteristic aspects on corrosion state of investigated elements. Based on the results of the investigations and experiments performed on site and in laboratory, there were proposed intervention measures on reinforced concrete elements, differentiated by the nature and intensity of the corrosion damages, as well by the aggressivity degree of environments, in order to assure the resistance, stability and durability of elements/structures and the normal conditions of service of electric transformer stations.
机译:本文介绍了30-40年后110 ... 400 kV变电站中用于电气设备维护的预制离心空心钢筋混凝土元件(柱,梁和支架)的使用性能研究结果。关于由侵蚀性试剂的腐蚀作用引起的损害,请参见“使用条款”。由于存在初始执行故障,在元件的存储,运输和蒙太奇期间出现变质以及缺乏有效的干预措施和这些元件的防腐蚀保护,腐蚀引起的损坏受到青睐/增加。指出了侵蚀剂对放置在电力和化学工业的侵蚀性环境以及电网特定城市侵蚀性环境中的变电站中离心钢筋混凝土构件的腐蚀作用。彩色照片说明了所研究元素的腐蚀状态的特征方面。根据现场和实验室的调查研究结果,提出了针对钢筋混凝土构件的干预措施,以腐蚀破坏的性质和强度以及环境的侵蚀程度来区分。元件/结构的电阻,稳定性和耐久性以及变电站的正常服务条件。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号