The hoisting system in the iron ore mine at LKAB in Kiruna is a fast changing load that affects power quality of the electrical system. In order to reduce the voltage variations and harmonic distortion to acceptable levels and at the same time increase production capacity it has been decided to install a static var compensator (SVC). The selection of ratings and configuration of the SVC has been based on a system study consisting of load- and power quality measurements as well as harmonic- and load-flow simulations. As a result of the study a SVC consisting of fixed harmonic filters and tyristor controlled reactor (TCR) has been selected. The results of simulations demonstrate that the selected SVC will reduce the voltage variations on the feeding 6 kV bus bar from 20% to less than 3% and at the 145 kV PCC from 6% to less than 2%. The total harmonic distortion will be reduced to less than 4,8% at the 6 kV bus bar and less than 1,5% at the 145 kV PCC. Thanks to the SVC, the production capacity of the hoisting system will increase by approx. 30%.
机译:基律纳LKAB的铁矿石矿中的起重系统是一个负载快速变化的负载,会影响电气系统的电能质量。为了将电压变化和谐波失真降低到可接受的水平,同时提高生产能力,已决定安装静态无功补偿器(SVC)。 SVC的额定值和配置的选择基于一项系统研究,包括负载和电能质量测量以及谐波和潮流仿真。研究的结果是,选择了由固定谐波滤波器和可控硅电抗器(TCR)组成的SVC。仿真结果表明,所选的SVC将6 kV馈电母线的电压变化从20%减小到小于3%,而145 kV PCC的电压变化从6%减小到小于2%。在6 kV母线上,总谐波失真将降低到小于4.8%,在145 kV PCC上,总谐波失真将降低到小于1.5%。多亏了SVC,提升系统的生产能力将增加约。 30%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号