The line loss ratio of Jiang-Chong 1305 Line has been continuously high since separate-line loss statistic method was employed in 1999. The yearly statistic line loss ratio is around 10%, which is far from the theoretical value of 0.054%. A series of reforms have been conducted for current transformer and the related measurement circuits as well as overhead lines of Jiang-Chong 1305. Parameters including harmonic impulse load are tested and analyzed. The reason for abnormal line loss is not found. In 2004, ECEPTRI conducted on-site verification of the current transformer. It was found that the overall deviation exceeds the limit due to the manufacturing defect, which results in the abnormal line loss of Jiang-Chong 1305. The analysis shows that verification of the current transformer should not be limited in laboratory. On-site verification should be strengthened to avoid abnormal line loss measurement.
机译:自从1999年采用单独线损统计方法以来,江崇1305线的线损率一直很高。年统计线损率约为10%,与理论值0.054%相去甚远。已对江创1305的电流互感器及相关的测量电路以及架空线路进行了一系列的改革。对包括谐波脉冲负载在内的参数进行了测试和分析。找不到异常线路丢失的原因。 2004年,ECEPTRI对电流互感器进行了现场验证。结果发现,由于制造缺陷,总偏差超过了极限,导致江崇1305的线损异常。分析表明,电流互感器的验证不应局限于实验室。应加强现场验证,避免异常线损测量。