Experimental investigation of internal short circuit faults leading to advanced incipient behavior and failure of a distribution transformer

机译:内部短路故障导致配电系统早期行为和故障的实验研究

获取原文

摘要

Transformer fault detection and diagnosis is becoming more important due to the restructuring of the electric power industry. In this era of deregulation, loading transformers to their optimum capacity is becoming normal practice, which in turn applies high stresses on the insulation of the transformers and increases the probability of occurrence of internal short circuit winding faults. Such faults can lead to catastrophic failure and hence cause outages. Utilities and other entities in the electric power business are therefore exploring ways of detecting these faults in transformers in the incipient stage. Terminal values, primary and secondary currents and voltages of the transformer convey information that can be used to detect internal transformer failures before developing a detection method. The behavior of these terminal values should be understood. In an effort to characterize the behavior of the terminal values of a transformer during internal short circuit and incipient faults, short circuit faults were staged on a 25 kVA, 7200 V/240 V/120 V two winding custom-built transformer. This paper discusses the results of the field experiments performed over a 19-month period. It presents time domain results of selected short circuit experiments. It also presents recordings of advance incipient-like behavior during the last set of experiments.
机译:由于电力行业的结构调整,变压器故障的检测和诊断变得越来越重要。在这个放宽管制的时代,将变压器加载到其最佳容量已成为一种惯例,这反过来又在变压器的绝缘上施加了很大的压力,并增加了发生内部短路绕组故障的可能性。此类故障可能导致灾难性故障,从而导致停机。因此,电力业务中的公用事业和其他实体正在探索在初期阶段检测变压器中这些故障的方法。变压器的端子值,一次和二次电流以及电压传达的信息可用于在开发检测方法之前检测内部变压器故障。这些终端值的行为应被理解。为了描述内部短路和初期故障期间变压器端子值的行为,在25 kVA,7200 V / 240 V / 120 V两绕组定制变压器上进行了短路故障。本文讨论了在19个月内进行的现场实验的结果。它提供了所选短路实验的时域结果。它还提供了最后一组实验期间类似先行行为的记录。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号