Modified deadbeat digital controller for UPS with 3-phase PWM inverter

机译:带有三相PWM逆变器的UPS的改进型无差拍数字控制器

获取原文

摘要

In this paper, a modified deadbeat control scheme is proposed for 3-phase PWM inverter control such as uninterruptible power supply (UPS). The deadbeat controller, which is generally constructed with voltage and current controller in UPS, is used for fast transient response, but this might have an instability due to the same pole placement of the double controller. To solve this instability problem, separation of pole placement can be considered, and it is performed by the proposed deadbeat control scheme. In this paper, this control scheme is called the modified deadbeat, which produces a first-order exponential response during one input step. As the overall controller is constructed by deadbeat control, the response of the proposed control system is fast and the structure of the controller is simple. In addition, the disturbance observer with full-order state is constructed, which can cancel the disturbances by adding a feedforward compensating loop in the controller and hence it can compensate the disturbances caused by a sudden load change in the UPS system.
机译:在本文中,提出了一种用于3相PWM逆变器控制的改进的止血控制方案,例如不间断电源(UPS)。通常用电压和电流控制器构造的死差控制器用于快速瞬态响应,但由于双控制器的杆放置相同,这可能具有不稳定性。为了解决这个不稳定问题,可以考虑杆放置的分离,并且由所提出的止血控制方案进行。在本文中,该控制方案被称为修改的止血,在一个输入步骤期间产生一阶指数响应。随着整体控制器由Deadbeat控制构建,所提出的控制系统的响应是快速的,并且控制器的结构很简单。另外,构造了具有全阶状态的干扰观察者,可以通过在控制器中添加前馈补偿环来取消干扰,因此它可以补偿由UPS系统中突然的负载变化引起的干扰。