首页> 外文会议>Conference on thermosense >Five important power line component anomalies
【24h】

Five important power line component anomalies

机译:五个重要的电力线组件异常

获取原文

摘要

During routine infrared surveys of switchyard, substation, distribution components and underground cable installations, several important anomalies have been identified. Five are reported on in this paper: (1) Moisture intrusion into high voltage polymer insulators; (2) Improper installation of a three phase service transformer set; (3) Improper tightening of a bushing connection; (4) Current transformer polyurethane coating encasement failure; (5) Underground cable and fuse enclosure insulator failure. In the first case the extremes of Florida weather, heat, humidity and moisture, contributed to the failure. In all cases, either improved manufacturing design or installation procedures could have prevented these problems. In addition to using infrared thermography as a survey tool, it is highly recommended to be used as a design and installation, baseline-checking tool.
机译:在Switchyard的常规红外测量期间,变电站,分配组件和地下电缆安装,已识别出几种重要的异常。本文报告了五个:(1)水分侵入高压聚合物绝缘体; (2)安装三相服务变压器集的不当; (3)衬套连接紧固不当; (4)电流互感器聚氨酯涂层口服损伤; (5)地下电缆和保险丝外壳绝缘子故障。在第一种情况下,佛罗里达天气,热,湿度和水分的极端,促成了失败。在所有情况下,改善的制造设计或安装程序都可能会阻止这些问题。除了使用红外热成像作为调查工具外,强烈建议用作设计和安装,基线检查工具。