Prediction of the Visible Plume from a Cooling Tower

机译:冷却塔中可见羽流的预测

获取原文

摘要

The visible plume from a cooling tower is sometimes considered to be a cause of nuisance such as icing, lower visibility, and obstructed sunshine. A reliable method of predicting the behavior of the visible plume is therefore expected to be established. In this study, the visible plume was predicted by means of computational fluid dynamics. The computational results were capable of reproducing the main features of the vissible plume. The length, width, and volume of the visible plume in various conditions agreed well with the measured values. Although it was not possible to represent the small fluctuations of the visible plume due to turbulence by the above simulation, this method is expected to become a useful tool in normalizing the scale of the visible plume.
机译:来自冷却塔的可见羽状物有时被认为是令人讨厌的原因,例如结冰,能见度较低和阳光直射。因此,期望建立一种可靠的预测可见羽流行为的方法。在这项研究中,可见羽状流是通过计算流体动力学来预测的。计算结果能够再现可见羽流的主要特征。在各种条件下,可见羽流的长度,宽度和体积与测量值非常吻合。尽管通过上述模拟无法表示出由于湍流引起的可见羽流的微小波动,但该方法有望成为标准化可见羽流尺度的有用工具。

著录项