A single line selection method cannot accurately identify all single-phase ground faults in low-current grounding systems, this paper proposes a new method for fault line selection of single-phase grounding faults based on fuzzy fusion based on the mutability, energy and polarity of zero-sequence current before and after the fault. This method first uses wavelet transform to reduce noise and divide the frequency of each feeder's transient zero-sequence current, continuing using the sensitivity of the zero-sequence energy method to detect the fault of the bus to detect the bus. If it is a fault of the bus, the line selection is ended. Otherwise, continue to find the membership of the three methods to the fault decision, and use fuzzy fusion to calculate the comprehensive fault credibility Degree, the highest credibility is the failure route. Matlab/Simulink is used to build a simulation model for experiments. The experimental results show that the method is not affected by the fault distance, initial fault angle, transition resistance, and noise; it selects lines accurately and can correctly identify bus faults.
机译:单线选择方法不能准确识别小电流接地系统中的所有单相接地故障,本文提出了一种基于模糊融合的可变性,能量和极性基于模糊融合的单相接地故障故障线选择新方法。故障前后的零序电流。该方法首先使用小波变换来减少噪声并划分每个馈线的瞬态零序电流的频率,然后继续使用零序能量方法的灵敏度来检测母线故障并检测母线。如果是总线故障,则线路选择结束。否则,继续寻找故障决策的三种方法的隶属度,并运用模糊融合计算出综合故障可信度,最高的可信度就是故障路径。 Matlab / Simulink用于建立用于实验的仿真模型。实验结果表明,该方法不受故障距离,初始故障角度,过渡电阻和噪声的影响。它可以准确地选择线路,并且可以正确地识别总线故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号