Analysis of factors affecting switching over voltage of main transformer in 500kV GIS booster station

机译:500kV GIS升压站主变切换电压影响因素分析

获取原文

摘要

Gas insulated switchgear (GIS) will form a fast transient overvoltage during operation, affecting the safe operation of the primary equipment connected to it, especially the transformer. In order to quantify the closing overvoltage of the main transformer of the GIS booster station, this paper uses the electromagnetic transient analysis software ATP-EMTP to establish a distributed parameter model. Mainly simulate the impact of GIS boost station equipment operation, the number of outgoing lines, the length of the pipeline connecting the transformer to the GIS bus, the distance between the arrester and the high-voltage winding on the main transformer closing overvoltage. Finally, the characteristics of the main transformer closing overvoltage were obtained.
机译:气体绝缘开关设备(GIS)在运行期间会形成快速的瞬态过电压,从而影响与其连接的主要设备(尤其是变压器)的安全运行。为了量化GIS升压站主变压器的合闸过电压,本文使用电磁暂态分析软件ATP-EMTP建立分布式参数模型。主要模拟GIS升压站设备运行的影响,引出线的数量,将变压器连接到GIS总线的管线的长度,避雷器与主变压器闭合高压之间的高压绕组之间的距离。最后,获得了主变压器闭合过电压的特性。