Ecodesign Chiller with a natural working fluid

机译:与自然工作流体的Ecodesign冷冻机

获取原文

摘要

According to the Regulation implementing the European Directive 2009/125/EC, from the year 2018, chillers with a rated cooling capacity not exceeding 2 MW must fulfil a series of "ecodesign" requirements to be placed on the market and/or put into service. Carbon dioxide (CO_2) as working fluids is, at least initially, not the best solution for air conditioning or chiller units due to its thermophysical properties. However, it is the purpose of this work to demonstrate that CO_2 could be a suitable refrigerant in chillers when certain design changes are implemented to the refrigeration system of the chiller. Simulations have shown that an improvement on the performance of chillers with CO_2 is obtained if ejectors are introduced to unload the compressors of the CO_2 unit. Applying the available expansion work within an ejector lifts the suction pressure of the compressors significantly. Experimental tests have been performed with the SuperSmart-Rack facility at NTNU/SINTEF. The operation conditions were specified in the aforementioned 'ecodesign' regulation to demonstrate that CO_2 chiller systems can actually fulfil the requirements.
机译:根据实施欧洲指令2009/125 / EC的监管,从2018年开始,具有不超过2兆瓦的额定冷却能力的冷却器必须履行一系列“ECODESIGN”要求,以便在市场上和/或投入使用。作为工作流体的二氧化碳(CO_2)至少最初不是由于其热神经性质而成为空调或冷却器单元的最佳解决方案。然而,当某些设计改变被实施到冷却器的制冷系统时,这项工作的目的是证明CO_2可以是冷却器中的合适制冷剂。仿真已经表明,如果引入喷射器以卸载CO_2单元的压缩机,则可以获得与CO_2的冷却器性能的改进。在喷射器内应用可用的膨胀工作显着提升压缩机的吸力压力。在NTNU / SINTEF的Supersmart-Rack设施进行了实验测试。在上述“Ecodesign”规则中规定了操作条件,以证明CO_2冷却器系统实际上可以满足要求。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号