To study the influence of grid-side equipment on the seismic performance of the converter transformer and bushing system, finite ele-ment models of the interconnected and standalone ±800kV UHV converter transformer and the grid-side equipment were established The sliding of the fittings at the top of grid-side bushings was simulated. The seismic response of bushings were analyzed, and the results indicated that the frequencies of the first 20 orders of the UHV converter transformer and bushing system is close to the seismic preeminent period, thus quasi-resonance is easy to occur. The grid-side equipment can significantly amplify the stress and displacement of grid-side bushing. The relative displacement in fittings is great in earthquake. Therefore, the coupling effect between the grid-side equipment and the converter transformer should be considered.
机译:为了研究电网侧设备对换流变压器和套管系统抗震性能的影响,建立了互连和独立的±800kV特高压换流变压器和电网侧设备的有限元模型。模拟了网格侧套管的顶部。对套管的地震响应进行了分析,结果表明,特高压换流变压器和套管系统的前20个阶次的频率接近于地震的突出期,因此容易发生准谐振。电网侧设备可以显着放大电网侧衬套的应力和位移。地震中配件的相对位移很大。因此,应考虑电网侧设备与换流变压器之间的耦合效应。