首页> 外文会议>IEEE International Conference on Advanced Power System Automation and Protection >An Adaptive Restart Method for DC Transmission Line in LCC-HVDC System
【24h】

An Adaptive Restart Method for DC Transmission Line in LCC-HVDC System

机译:LCC-HVDC系统中直流输电线路的自适应重启方法

获取原文

摘要

DC-line fault recovery sequence (DFRS) is widely implemented in LCC-HVDC system to realize fast recovery in case of temporary fault. When permanent fault occurs, restart still happens several times as preset, resulting in repeated impacts and reducing the stability and reliability of the system. An adaptive restart for DC line fault is studied in this paper to deal with this problem. Firstly, the converter valves states and DC voltage characteristics under temporary fault and permanent fault are analyzed respectively. Then, a method based on DC voltage control is proposed to distinguish different fault states. Current DFRS strategy is improved by adding this process, through which the fault pole will only restart after the temporary fault disappearing, while directly blocked when a permanent fault is recognized. Fault handling time can be shortened and negative effects of DC line fault are minimized. The simulation results verify feasibility and effectiveness of proposed method.
机译:LCC-HVDC系统广泛采用直流线路故障恢复序列(DFRS),以在出现临时故障时实现快速恢复。当发生永久性故障时,重启仍会按照预先设定的次数进行几次,从而造成重复的影响并降低系统的稳定性和可靠性。为了解决这个问题,本文研究了直流线路故障的自适应重启。首先,分别分析了临时故障和永久故障下的换流阀状态和直流电压特性。然后,提出了一种基于直流电压控制的方法来区分不同的故障状态。通过添加此过程可以改进当前的DFRS策略,通过该过程,故障极仅在临时故障消失后才会重新启动,而在识别出永久性故障时才直接阻塞。可以缩短故障处理时间,并将直流线路故障的负面影响最小化。仿真结果验证了该方法的可行性和有效性。

著录项