首页> 外文会议>IEEE International Conference on Advanced Power System Automation and Protection >Missing-operation Risk of Directional Comparison Teleprotection with Photovoltaic Power Integration
【24h】

Missing-operation Risk of Directional Comparison Teleprotection with Photovoltaic Power Integration

机译:带有光伏电源集成的定向比较远距离保护的误操作风险

获取原文

摘要

Although the ac fault current provided by photovoltaic (PV) power plant is limited as a weak-infeed power or a electric load, the voltage and current directions are different from conventional synchronous source, since the current is highly controlled by the PV inverter. This paper investigates the measured impedance and the distance directional element of PV side line protections. The impedance trajectory are drawn and compared with conventional power source. Simulation result shows that the directional comparison teleprotections may miss operate under a line internal fault, since the measured impedance drops into the negative direction area, even though the weak-infeed tripping function is activated.
机译:尽管将光伏(PV)电厂提供的交流故障电流限制为弱馈电功率或电负载,但由于电流由PV逆变器高度控制,因此电压和电流方向与常规同步电源不同。本文研究了光伏侧线保护装置的测量阻抗和距离方向元件。绘制阻抗轨迹并将其与常规电源进行比较。仿真结果表明,即使激活了弱馈跳闸功能,由于测得的阻抗下降到负方向区域,定向比较远距保护也可能会在线路内部故障下丢失操作。