This paper investigates the use of smart meters to detect hazardous conditions on rural LV networks with a TN-C-S earthing system. Various hazards that can be detected by taking voltage and current measurements at the transformer and customer installations are identified and evaluated. These hazards include PEN conductor failure, transformer LV earth electrode high impedance failure and hazardous conditions that lead to current unbalance. Developmental smart meters were installed on an experimental laboratory feeder. Experimental results show that these hazards can be detected and communicated to the network utility via ZigBee and GPRS.
机译:本文研究了使用智能电表通过TN-C-S接地系统检测农村低压网络中的危险情况。通过对变压器和客户设备进行电压和电流测量,可以识别和评估各种可以检测到的危险。这些危险包括PEN导体故障,变压器LV接地电极高阻抗故障以及导致电流不平衡的危险情况。开发型智能电表安装在实验实验室给料机上。实验结果表明,可以检测到这些危险,并通过ZigBee和GPRS将其传达给网络实用程序。