摘要

Dissolved Gas Analysis (DGA) is one of the most common methods used to diagnosis the fault types in the transformers. The fault types which occur in the power transformer are categorized as partial discharge, low discharge energy, high discharge energy, low thermal fault, medium thermal fault and high thermal fault. These faults can be specified according to the concentrations of each dissolved in the transformer oil. In this paper, the modified technique result depends on the outputs of the three techniques (new approach, conditional probability, Duval). The modified technique was prepared to increase the accuracy of the detection of the transformer fault types. It was constructed based on 386 samples that were collected from the Egyptian Electricity Transmission company (EETC) – Central Chemical Laboratories, and were known their actual faults. The result of the modified DGA technique indicated an increase of the diagnostic accuracy rather than the other DGA techniques.
机译:溶解气体分析(DGA)是用于诊断变压器中故障类型的最常用方法之一。电力变压器中发生的故障类型分类为局部放电,低放电能量,高放电能量,低热故障,中热故障和高热故障。这些故障可以根据溶解在变压器油中的每种浓度指定。在本文中,修改的技术结果取决于三种技术的输出(新方法,条件概率,杜瓦尔)。准备改进的技术以提高变压器故障类型的检测的准确性。它基于从埃及电力传输公司(EETC) - 中央化学实验室收集的386个样本,并已知其实际故障。修改的DGA技术的结果表明诊断准确性的增加而不是其他DGA技术。