首页> 外文会议>IEEE Industry Applications Society Annual Meeting >Optimum resistive type fault current limiter: An efficient solution to achieve maximum fault ride-through capability of fixed speed wind turbines during symmetrical and asymmetrical grid faults
【24h】

Optimum resistive type fault current limiter: An efficient solution to achieve maximum fault ride-through capability of fixed speed wind turbines during symmetrical and asymmetrical grid faults

机译:最佳电阻型故障电流限制器:一种有效的解决方案,可在对称和非对称电网故障期间实现定速风力涡轮机的最大故障穿越能力

获取原文

摘要

This paper proposes an optimum resistive type fault current limiter (OR-FCL) as an efficient solution to achieve maximum fault ride-through (FRT) capability of fixed speed wind turbine (FSWT) during various grid faults. A dedicated control circuit is designed for the OR-FCL in a way that enables it to insert an optimum value of resistance in the FSWT's fault current path. Therefore, the OR-FCL significantly improves transient behavior of the FSWT. It will be shown that, the optimum resistance value depends on fault location and pre-fault active power. So, the control circuit of the proposed OR-FCL is capable to calculate the optimum resistance value for all the pre-fault conditions. In this way, the FSWT achieves its maximum FRT capability during symmetrical and asymmetrical faults even at zero grid voltage, as recommended by some new grid codes. The analytical analysis is provided in detail to highlight the process of calculating the optimum resistance of the OR-FCL. Moreover, the effect of the resistance value of the OR-FCL on the FRT behavior of FSWT is investigated, too. To show the high efficiency of the proposed OR-FCL, its performance during various operation conditions of the FSWT, will be studied. It will be proved that each operation condition needs its own optimum resistance value during the fault to achieve the maximum FRT capability of the FSWT. The comprehensive sets of simulations are carried out in PSCAD/EMTDC software; the results approve efficiency and effectiveness of the proposed approach.
机译:本文提出了一种最佳的电阻型故障电流限制器(OR-FCL),作为在各种电网故障期间实现定速风力涡轮机(FSWT)的最大故障穿越能力(FRT)的有效解决方案。为OR-FCL设计了专用的控制电路,以使其能够在FSWT的故障电流路径中插入最佳电阻值。因此,OR-FCL显着改善了FSWT的瞬态行为。结果表明,最佳电阻值取决于故障位置和故障前有功功率。因此,提出的OR-FCL的控制电路能够计算出所有故障前条件下的最佳电阻值。这样,即使在电网电压为零的情况下,FSWT也可在对称和非对称故障期间达到最大FRT能力,这是一些新的电网法规所建议的。详细提供了分析分析,以突出显示OR-FCL最佳电阻的计算过程。此外,还研究了OR-FCL的电阻值对FSWT FRT行为的影响。为了显示提出的OR-FCL的高效率,将研究其在FSWT的各种操作条件下的性能。可以证明,在故障期间,每种操作条件都需要具有自己的最佳电阻值,以实现FSWT的最大FRT能力。全面的模拟集在PSCAD / EMTDC软件中进行;结果证明了该方法的有效性和有效性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有