Application of Accident Total Signal in L30 Lead Protection of Ur Series in Ge Company

机译:在GE公司L30系列中L30铅保护中的事故总信号

获取原文

摘要

With the secondary circuit and relay protection which take part in protection, measurement and monitoring of primary equipment are also in the process of continuous optimization, so as one important signal which provides alarm information for operating personnel, accident total signal should draw the attention of professional personnel of relay protection. In one substation, protection cabinet of transformer compartment is configured by UR series L30 short lead protection device, operation box and 86 trip block relay of GE company; after the protection trips, 86 trip block relay takes action and cuts off the control circuit, but Positioning relay (HWJ)/(Jump relay) TWJ cannot act normally to feed back the location of circuit breaker, which results in the accident total signal always cannot be given out normally. This paper will carry out technical analysis on secondary circuit and come up with solution.
机译:通过参与保护,对主要设备的测量和监控的二级电路和继电器保护也在连续优化过程中,因此作为提供警报信息的一个重要信号,为操作人员提供警报信息,事故总信号应引起专业的注意继电保护人员。在一个变电站中,电压器隔室的保护柜由GE公司的UR系列L30短铅保护装置,操作盒和86跳闸块继电器配置;在保护跳闸之后,86个跳闸块继电器采取动作并切断控制电路,但定位继电器(HWJ)/(跳转继电器)TWJ不能正常行动,以便回馈断路器的位置,从而导致事故总信号总是导致总信号总量的总信号不能正常发出。本文将对次要电路进行技术分析,并提出解决方案。