首页> 外文会议>International Conference on Building Energy and Environment >Study of CO2 Transcritical Cycle Heat Pump Water Heater
【24h】

Study of CO2 Transcritical Cycle Heat Pump Water Heater

机译:CO2跨临界循环热泵热水器的研究

获取原文

摘要

A CO2 transcritical cycle heat pump water heater was set up and the experiments were conducted in this study.The efficiency of the CO2 compressor is calculated based on the testes data,the water heater was tested at different operating conditions.The results show that the efficiency of system increases when the temperature of ambient become higher and inlet water temperature keeps constant,so the system can get high efficiency at the warm season when more hot water is needed for residents.COPh (coefficient of performance of heating) of heat pump system can reach 3.0 when the outlet temperature of water is 60°C.The higher inlet temperature of water is not good for performance of CO2 transcriticai cycle heat pump,so the straight flow type water heater can help to get higher COPh.In this paper,it is found that the COPtotal of system can reach above 5.0 when both refrigeration and heating water can be utilized at the same time.But the operation condition must be control and the system should be redesign for application.
机译:建立了CO2超临界循环热泵热水器,并进行了实验。根据睾丸数据计算出CO2压缩机的效率,并在不同工况下进行了测试。当环境温度升高且进水温度保持恒定时,系统的温度会升高,因此当居民需要更多热水时,系统可以在温暖季节获得较高的效率。热泵系统的COPh(加热性能系数)可以当出水温度为60°C时达到3.0。进水温度过高不利于CO2循环循环热泵的性能,因此直流式热水器可以帮助获得更高的COPh。发现制冷和热水同时使用时,系统的总COP值可以达到5.0以上。请重新设计应用程序。