首页> 外文会议>CMD 2008;International Conference on Condition Monitoring and Diagnosis >Ultra-high Frequency Spectral Characteristics of Partial Discharge in Insulation Oil Sun-geun Goo, Hyeongjun Ju, Kijun Park, Kiseon Han, Jinyul Yoon Korea Electric Power Research Institute, Korea Electric Power Corporation 65 Munji-ro,Yusong-gu, Daejeon,
【24h】

Ultra-high Frequency Spectral Characteristics of Partial Discharge in Insulation Oil Sun-geun Goo, Hyeongjun Ju, Kijun Park, Kiseon Han, Jinyul Yoon Korea Electric Power Research Institute, Korea Electric Power Corporation 65 Munji-ro,Yusong-gu, Daejeon,

机译:绝缘油局部放电的超高频频谱特性谷Sun根,鞠亨俊,纪俊公园,韩纪勋,金雨尹韩国电力科学研究院,韩国电力公司大田市裕城市区文治路65

获取原文

摘要

We have designed and manufactured four types of typical defects found in power transformers to simulate partial discharge(PD) in oil insulated power transformers. Stable PD signals were generated by applying AC voltages on to the PD cells. We measured spectral response of PD signals from these defects using our Ultra-high frequency(UHF) PD measuring system and apparent discharge using IEC60270 PD detector simultaneously. Partial discharges from the defects in oil generated well detectable UHF signal up to about 2 GHz. UHF PD patterns were recorded and analyzed for each defect types. The phase resolved partial discharge(PRPD) patterns of defect obtained from UHF range were different from each other. The patterns of UHF PD signals were also different from those obtained from that of conventional method. Type of defect could be identified by obtaining PRPD patterns.
机译:我们已经设计并制造了四种类型的电力变压器典型缺陷,以模拟油绝缘电力变压器的局部放电(PD)。通过在PD电池上施加交流电压来生成稳定的PD信号。我们使用我们的超高频(UHF)PD测量系统测量了来自这些缺陷的PD信号的频谱响应,并使用IEC60270 PD检测器同时测量了视在放电。石油中的缺陷产生的局部放电可产生高达2 GHz的可很好检测的UHF信号。记录并分析每种缺陷类型的UHF PD模式。从超高频范围获得的缺陷的相分辨局部放电(PRPD)模式彼此不同。 UHF PD信号的模式也与常规方法不同。缺陷的类型可以通过获取PRPD模式来识别。

著录项