首页> 外文会议>Electricity Distribution, 2005. CIRED 2005 >Analysis and prevention inquiry on break of 10kV aerial insulated wire caused by lightning stroke
【24h】

Analysis and prevention inquiry on break of 10kV aerial insulated wire caused by lightning stroke

机译:雷击造成10kV架空绝缘电线断裂的分析及预防性探究

获取原文

摘要

The method to prevent 10kV aerial insulated wire from breaking caused by lightning stroke is put forward according to the mechanism of the break of 10kV aerial insulated wire caused by lightning stroke and the motion rules of power frequency arc via the probability calculation and analysis of lightning stroke flashover It is verified through test that the phenomenon of the lightning stroke discharge can occur between the gap of high voltage electrode and low voltage electrode of the special arc protection device. It is also able to effectively lead the arc root of power frequency arc after lightning flashover, protecting the insulated wire from being burnt and broken and making it able to withstand above five times of large current arc burning of power frequency to achieve the expected effect.
机译:根据雷击的概率计算和分析,结合雷击引起的10kV架空绝缘线断裂的机理和工频电弧的运动规律,提出了防止雷击引起的10kV架空绝缘线断裂的方法。闪络通过试验证实,在特殊电弧保护装置的高压电极和低压电极之间的间隙之间会发生雷击放电现象。它还能有效地引导雷电击穿后的工频电弧的电弧根,保护绝缘电线不被烧毁和断裂,使其能够承受工频大电流电弧燃烧的五倍以上,从而达到预期的效果。