CO_2 DEMAND CONTROLLED VENTILATION USING ON-OFF CONTROL FOR ENERGY SAVINGS

机译:使用开/关控制的CO_2需求控制通风以节省能源

获取原文

摘要

An on-off type of control has been modeled using a FORTRAN program that solves the mass balance equation for CO_2 buildup in each floor of a typical ten story office building. The approach is based on monitoring CO_2 concentration in the building and admitting sufficient outside air by opening and closing the dampers to ensure that the air quality is maintained within specified limits. To investigate this, two hourly occupancy profiles used in the FORTRAN program were modeled in DOE-2.1 simulation program using variable air volume and constant air volume systems. Simulation was performed for a base case using ASHRAE's recommended minimum ventilation rate of 20 cfm/person. For DCV case, DOE-2.1 simulation was performed using the minimum ventilation rates based on the CO_2 concentration resulted from the FORTRAN program. Results show small savings in energy consumption for DCV case.
机译:已经使用FORTRAN程序对控制的开关类型进行了建模,该程序解决了典型的十层办公楼各层中CO_2堆积的质量平衡方程。该方法基于监视建筑物中的CO_2浓度,并通过打开和关闭风门来吸收足够的外部空气,以确保将空气质量保持在指定的范围内。为了对此进行调查,在DOE-2.1模拟程序中使用可变风量和恒定风量系统对FORTRAN程序中使用的两个小时的占用情况进行了建模。使用ASHRAE的建议最小通风量为20 cfm /人,对基本案例进行了模拟。对于DCV情况,基于FORTRAN程序得出的CO_2浓度,使用最小通风率进行了DOE-2.1仿真。结果表明,在DCV情况下,能耗节省很小。